Upright sprinkler

Harness HS200 fire sprinklers are upright (SSU), standard response, frangible glass bulb automatic sprinklers that are CE marked, according to UL and EN and UL listed bulbs.

They are standard orifice fire sprinklers for installation in fire sprinkler systems designed in accordance with standard installation rules, e.g., EN12845 or the requirements of the authority having jurisdiction.

SSU upright sprinklers produce a hemispherical water distribution pattern below the deflector. In the instance of fire, the heat causes the fluid in the glass bulb to expand which shatters the glass and releases the spring seal assembly. Water flows from the orifice onto the sprinkler deflector which diffuses the water into a uniform spray pattern which extinguishes or controls the fire.

K FACTOR 80 (5.6)
STANDARD ORIFICE SIZE 15 mm (½”)
STANDARD THREAD SIZE ½” NPT
RESPONSE Standard Response
BULB 5 mm
MAXIMUM WORKING PRESSURE 12.1 bar (175 psi)
FINISH Brass, chrome and white paint finish. Special RAL colors available on request
APPROVALS LPCB, CE, according  to UL

 

Nominal Operating Temperature Bulb Color
57ºC (135ºF) Orange
68ºC (155ºF) Red
79ºC (175ºF) Yellow
93ºC (200ºF) Green
141ºC (286ºF) Blue

 