Harness HS200 fire sprinklers are upright (SSU), standard response, frangible glass bulb automatic sprinklers that are CE marked, according to UL and EN and UL listed bulbs.
They are standard orifice fire sprinklers for installation in fire sprinkler systems designed in accordance with standard installation rules, e.g., EN12845 or the requirements of the authority having jurisdiction.
SSU upright sprinklers produce a hemispherical water distribution pattern below the deflector. In the instance of fire, the heat causes the fluid in the glass bulb to expand which shatters the glass and releases the spring seal assembly. Water flows from the orifice onto the sprinkler deflector which diffuses the water into a uniform spray pattern which extinguishes or controls the fire.
K FACTOR | 80 (5.6) |
STANDARD ORIFICE SIZE | 15 mm (½”) |
STANDARD THREAD SIZE | ½” NPT |
RESPONSE | Standard Response |
BULB | 5 mm |
MAXIMUM WORKING PRESSURE | 12.1 bar (175 psi) |
FINISH | Brass, chrome and white paint finish. Special RAL colors available on request |
APPROVALS | LPCB, CE, according to UL |
Nominal Operating Temperature | Bulb Color |
57ºC (135ºF) | Orange |
68ºC (155ºF) | Red |
79ºC (175ºF) | Yellow |
93ºC (200ºF) | Green |
141ºC (286ºF) | Blue |