HS100 Pendent Standard Response Sprinkler

HS100fire sprinklers are pendent, standard response, frangible glass bulb automatic sprinklers.

They are made according to CE Marked, LPCB, VdS, FM approved, UL listed bulbs, standard orifice fire sprinklers for installation in fire sprinkler systems.

HS100 Sprinklers produce a hemispherical water distribution pattern below the deflector. In the instance of fire, the heat causes the fluid in the glass bulb to expand which shatters the glass and releases the spring seal assembly. Water flows from the orifice onto the sprinkler deflector which diffuses the water into a uniform spray pattern which extinguishes or controls the fire.

Design Coverage

HS100Spray Pendent Sprinkler for installing only in pendent position giving hemispherical discharge below the deflector with little or no water being discharged upwards. For sprinkler coverage area and placement refer to NFPA 13 or EN 12845 standards or other Installation rules for automatic sprinkler systems as required by the authority having jurisdiction. The following details are provided for information only.

 

K factor K115 (K8.0)
Standard Orifice Size  20mm (¾”)
Thread Size ¾” NPT, R3/4
(¾” BSPT) available on special order
Max. Working Pressure 12 bar (175 psi)
Min. Operating Pressure 0.5 bar (7psi)
Factory Pressure Test 34 bar (500 psi)
Weight 79 g (2.8 oz)
Fitted with Bulb Protector Remove after installing sprinkler

Nominal Operating Temperature Bulb Colour
57ºC (135ºF) Orange
68ºC (155ºF) Red
79ºC (175ºF) Yellow
93ºC (200ºF) Green
141ºC (286ºF) Blue

 